DN40 float trap main valve replacement
Spirax Sarco 0666180 is a DN40 main valve assembly for the 10 bar differential-pressure versions of the FT43, FT44 and FT47 ball float steam traps. The main valve is the internal mechanism that opens the condensate discharge path as the float rises. The material number identifies the spare needed for this combination of trap size and pressure class. Check the connection orientation on the installed trap before ordering so the replacement matches the original mechanism and inlet arrangement.
What the assembly does
Condensate entering the trap raises the float. Its lever operates the main valve, allowing condensate to discharge as it forms. As the liquid level falls, the float drops and the main valve closes. At start-up, the air vent provides a separate route for air to leave the trap before hot condensate closes the vent. The distinction matters during maintenance: the main valve, float and air vent perform different jobs and have separate spare-parts entries in the DN40 documentation.
The main valve assembly sits inside the body at the condensate discharge mechanism. When ordering for an overhaul, identify the main valve gasket at the mechanism and the cover gasket at the body-to-cover joint separately. If the service scope includes the float or air vent, confirm those parts at the same time. This lets maintenance staff plan for the parts required at each joint and avoids assuming that a main valve assembly by itself can address every cause of poor drainage.
Match the size, pressure class and connection orientation
Start with the full trap designation on the nameplate. FT43, FT44 and FT47 identify the host series, while DN40 and the -10 designation narrow the spare selection. The material list also cross-references the DN40 FT46-10. For an FT46 enquiry, provide the full nameplate and original configuration so the correct assembly can be confirmed. The reference for the FT43 host is the FT43 ball float steam trap product page, which describes the complete trap.
DN40 refers to the nominal size of the trap. A DN50 unit can share the same illustration and still require a different replacement assembly. The same distinction applies when two mechanisms are both listed as a main valve assembly but serve different differential-pressure versions. If the spare is being bought from an old parts list or from a removed mechanism, reconcile the part number with the host trap’s nameplate and piping arrangement before ordering.
The 10 bar figure is the maximum operating differential for the -10 variant. It describes the difference between inlet and outlet pressure across the trap. Condensate-return backpressure contributes to the outlet side of that calculation. The complete trap’s allowable pressure, operating limits and temperature must be checked separately in the technical data for that host model. When sizing a new drainage point, use the complete trap’s capacity data at the available differential pressure and condensate load. When servicing an existing DN40 trap, use the installed pressure class to identify the replacement mechanism.
Connection orientation matters because the inlet arrangement changes. The manufacturer illustrates a plate over the inlet on the horizontal DN40 arrangement, retained by the mechanism bolts. It keeps the entering flow from interfering with float motion. The vertical FT43, FT44 and FT47 configurations are documented without the horizontal erosion deflector. A photograph of the body connections and flow arrow, together with the nameplate, helps distinguish the installation before the trap is opened for service.
Information to include when requesting a replacement
Quote 0666180 and give the full trap designation, DN40 nominal size, 10 bar differential-pressure class and horizontal or vertical connection orientation. Include a legible nameplate photograph if the pressure suffix is unclear. State whether the work also calls for a cover gasket, float or air vent. The way these assemblies work together is explained in the steam trap guide, which is useful when the service team is still identifying the affected part.
For a matching installation, the 0666180 main valve assembly gives maintenance teams a way to renew the condensate discharge mechanism within the existing trap body. Use the technical and maintenance information below to cross-check the part group, the inlet baffle arrangement and the DN40 mechanism fastener specification before returning the trap to service.
Technical Information
DN40 main valve data from TI-S02-21 Issue 14, TI-S02-14 Issue 18, TI-P142-01 Issue 15 and TI-P143-01 Issue 15.
| Trap version | Size | Maximum differential pressure |
|---|---|---|
| FT43-10 | DN40 | 10 bar |
| FT44-10 | DN40 | 10 bar |
| FT47-10 | DN40 | 10 bar |
| FT46-10 | DN40 | 10 bar |
| Item | Component and material |
|---|---|
| 5 | Main valve assembly, stainless steel |
| 6 | Main valve assembly gasket, reinforced exfoliated graphite |
| 7 | DN40 main valve assembly bolts, stainless steel |
| 12, 26 | Erosion deflector and inlet plate as shown for the applicable horizontal mechanism |
| 8 | Ball float and lever, a separate spare-parts entry |
The DN40 horizontal spare-parts group is identified as items 5, 6, 7, 12 and 26 in the shared drawings. Specify horizontal or vertical connections when ordering. The DN40 vertical FT43, FT44 and FT47 traps do not use the horizontal erosion deflector.
Installation and Maintenance Guide
Instructions for the DN40 main valve mechanism from IM-S02-30, Issue 16, Sections 1, 3, 4, 6.1 and 6.3.
Isolate the trap before opening
- Use qualified personnel, suitable tools, protective equipment and the site’s permit-to-work procedure. Assess the effect of isolation on the rest of the system, including its vents and protective devices.
- Operate isolating valves gradually. Isolate the pressure and vent the trap safely to atmospheric pressure. Consider double block and bleed and lock or label the isolation valves where appropriate. A gauge reading of zero alone does not establish safe depressurisation.
- Let the equipment cool. Take precautions for hot surfaces and retained fluid during dismantling. Handle and dispose of the old cover gasket carefully because it contains a thin stainless steel support ring.
- With suitable isolation the trap may be serviced in the line. Ensure a safe working position and enough clearance for cover removal.
Fit the DN40 main valve assembly
- With the trap isolated and the cover removed, undo the four mechanism fasteners (item 7).
- Remove the main valve assembly (item 5) and its gasket (item 6). Make sure the gasket faces are clean and dry.
- Fit the new gasket and main valve assembly. On the horizontal DN40 configuration, place the supplied inlet baffle over the inlet port under the mechanism retaining bolts, as shown in Figure 9.
- Tighten the fasteners evenly to the value in the table. Ensure all joint faces are clean and the locating dowel engages the cover during reassembly. Use the complete instructions for the trap’s cover fasteners and reassembly requirements.
| Item | Across flats | Thread size | Torque |
|---|---|---|---|
| 7 | 10 mm A/F | M6 × 20 | 10–12 N·m (7.0–9.0 lbf·ft) |
Check orientation and operation
Confirm that the body arrow matches the direction of flow. The float arm must lie in a horizontal plane so the float can rise and fall vertically. Check the assembled system for correct operation and test any alarms or protective devices after maintenance.