LSB31 limit switch box for valve position indication
The Spirax Sarco LSB31 is a limit switch box for indicating the open or closed position of a valve operated by a BVA300 series actuator. It combines a local position indicator with two mechanical single-pole double-throw (SPDT) contact switches. The switching points can be adjusted over the actuator's range, helping the electrical indication match the positions required by the installation.
A stainless-steel linkage kit is included for direct mounting to BVA300 series actuators. The box and its mounting bracket form part of the valve automation assembly; the actuator and valve must be selected separately for the duty. The position indication is based on the switch box and actuator mechanism, so the complete assembly and its feedback should be checked during commissioning.
When selecting a compatible Spirax Sarco ball valve, check the complete valve and BVA300 actuator assembly for the duty.
Open and closed position feedback
The two SPDT switches provide contact outputs for the configured switching positions. They can be used as part of a correctly designed indication arrangement to report valve position to the associated control or monitoring equipment. The transparent dome indicator on the top of the enclosure gives a local open/closed indication, while the switch contacts serve the connected electrical circuit.
Decide which actuator positions should operate the contacts and how those signals will be used before setting the cams. The published documentation describes adjustable switching points; it does not specify a continuous position measurement for the LSB31. A position signal should not be treated as proof of the flow condition or of valve seat tightness.
Enclosure and operating environment
The standard LSB3 series data lists an IP67 enclosure and an ambient temperature range of −20 °C to +80 °C. The case is cast aluminium, and the standard position indicator is a 0°–90° dome type. The connection socket has eight terminals. The dimensions drawing shows two PG13.5 cable entries; suitable cable glands and correct sealing are necessary when wiring the unit.
The technical information lists IP68 protection and a −40 °C to +100 °C ambient range in its optional column. These are configuration options, not assumed characteristics of every LSB31. Confirm the selected unit and its nameplate against the location, cable entry arrangement and environmental conditions before ordering or installation.
Mounting and installation planning
The supplied bracket is designed for an actuator with a NAMUR VDI/VDE 3845 interface. When selecting a complete assembly, confirm that the actuator interface and linkage suit the unit, and allow access to the cover, cable entries and position indicator. The manufacturer's instructions call for the switch-box shaft to be aligned with the actuator before the drive is engaged and the box is fastened with the supplied bolts.
Where adjustment is required, the cover is removed and the cams are set to the required switching positions. Electrical work must be planned around the unit's own wiring label and the installation's electrical requirements. The published LSB31 data identifies the contact type but does not state a contact voltage or current rating; confirm the electrical rating and any required approval for the actual unit before connection.
Commissioning and maintenance
Before work on the switch box, isolate the electrical supply and follow the site's procedures for the associated valve and process system. After installation or maintenance, verify operation of the complete assembly and test any related alarms or protective devices. Correct replacement of the cover gasket and tightening of the cable gland are necessary to maintain the enclosure's protection rating.
The installation guide states that no routine maintenance is required for the unit, although the switch settings can be checked periodically. It does not list replacement parts for the switch box. When requesting a unit, identify it as LSB31 and confirm the actuator, mounting interface, enclosure requirement, ambient conditions and electrical circuit details with the supplier.
Technical information
The LSB31 limit switch box has two mechanical SPDT contacts for valve open and closed position indication. A stainless-steel linkage kit is supplied for direct mounting to BVA300 series actuators. Switching points are adjustable over the actuator range.
| Characteristic | Standard data |
|---|---|
| Switches | 2 × mechanical SPDT contact switches |
| Enclosure protection | IP67 |
| Ambient temperature | −20 °C to +80 °C |
| Case | Cast aluminium |
| Outer cover | Epoxy–polyester |
| Connection socket | 8 terminals |
| Position indicator | 0°–90° dome type |
| Mounting kit | NAMUR, SS1 or SS2 stainless steel |
| Cable entries | 2 × PG13.5 |
The series technical sheet lists IP68, a −40 °C to +100 °C ambient range, a nylon outer cover, three-way L-port or T-port indication, and SS3 or MT1 mounting kits as options. Confirm availability and suitability for the ordered LSB31. A stainless-steel 316L case is not available for the LSB3 series.
Dimensions are approximate and shown in the dimension drawing above. Local regulations may restrict use below the stated conditions. Source: TI-P372-26, CTLS Issue 5.
Installation and Maintenance Guide
Follow the complete manufacturer’s installation and maintenance instructions IM-P372-27 and the information on the supplied unit. The following sections cover the LSB31-specific application of that document.
Safety information
Installation, commissioning, use and maintenance must be carried out by qualified personnel in accordance with the operating instructions and applicable plant and pipeline safety procedures. Isolate the mains supply before carrying out any work on the switch box.
- Check the nameplate and confirm that the mechanical switches, materials and permitted conditions are suitable for the intended installation. Arrange protective devices if the associated system could exceed permitted limits or a malfunction could create dangerous overpressure or overtemperature.
- Assess external stresses, safe access, lighting, lifting needs and hazards in and around the associated system, including hazardous fluids, lack of oxygen, hot surfaces, fire, noise and moving machinery.
- Consider the effect of electrical and valve isolation on personnel, vents, alarms and protective devices. Open and close isolation valves gradually to avoid system shocks.
- When work involves a pressurised system, isolate and vent pressure safely to atmosphere. Consider double isolation and locking or labelling closed valves; a zero gauge reading alone does not prove that the system is depressurised.
- Allow equipment to cool after isolation. Use suitable tools and protective clothing, follow any permit-to-work procedure and assess manual-handling risks. The manufacturer warns that the external surface may reach 100 °C (212 °F) at maximum permitted operating conditions.
- Take care when dismantling equipment that is not self-draining, and protect susceptible equipment from freezing. Dispose of the product with due care. When returning equipment, identify contamination or damage hazards and provide the appropriate safety information.
Installation and cam adjustment
- Confirm the actuator interface and the mounting arrangement. The supplied stainless-steel bracket is suitable for an actuator with a NAMUR VDI/VDE 3845 interface.
- Manually turn the box shaft to align it with the actuator before engaging the drive shaft. Fasten the box to the actuator using the bolts provided.
- If adjustment is required, loosen the four cover screws, remove the cover and readjust the cams to the required positions. Units are supplied with 0°–90° cam adjustment.
Wiring
With the electrical supply isolated, introduce the cable through the gland and connect the conductors to the terminal strip in accordance with the wiring label on the outside of the LSB31. To maintain the IP rating, carefully place the gasket between the cover and the enclosure, reassemble the cover and tighten the cable gland.
See the LSB31 switch and terminal diagram above.
Commissioning, operation and maintenance
After installation or maintenance, ensure that the system functions correctly and test any alarms or protective devices. The limit switches indicate valve open and closed positions; the switching points can be adjusted over the actuator range.
No routine maintenance is required. Switch settings may be checked periodically. The manufacturer lists no available spare parts for these units.
Download installation and maintenance instructions IM-P372-27 (PDF)