KE73 EP6 PN9123E Pneumatic Control Valve Assembly

Control systems > Control valves

KE73 EP6 PN9123E Pneumatic Control Valve Assembly

Small-bore pneumatic control valve assembly combining a KE73 two-port globe valve, an EP6 linear positioner and a PN9123E spring-extend diaphragm actuator.

Genuine Spirax Sarco industrial steam product Engineered for energy efficiency and system safety Backed by worldwide application engineering support

Quick facts

Model / CodeKE73-EP6-PN9123E
CategoryControl valves
ManufacturerSpirax Sarco

A small-bore modulating valve, actuator and positioner package

The KE73 EP6 PN9123E control valve assembly combines a KE73 Spira-trol two-port valve, an EP6 electro-pneumatic positioner and a PN9123E pneumatic diaphragm actuator. The valve controls process flow, the actuator supplies linear motion, and the positioner regulates pneumatic output in response to a 4–20 mA command and stem-position feedback. Specify the three components together so the valve stroke, actuator force and feedback linkage are checked as one assembly.

The selection basis is the small-bore EN K-series valve with 20 mm travel, as shown in the Spira-trol technical information for DN15–DN50. The PN9123E belongs to the 20 mm PN9100 actuator frame, and the EP6 mounting table lists that frame with the Spira-trol valves in the same size band. This overlap identifies the sizes to evaluate. The actual combination still depends on available flange and trim options and the force needed to close against the project differential pressure.

Manufacturer outline of the flanged small-bore Spira-trol K-series valve body
Flanged small-bore K-series valve outline. Source TI-S24-71, page 1.

Size the valve for the process

KE73 identifies a flanged K-series valve with an equal-percentage characteristic and spheroidal graphite cast iron construction. Equal-percentage trim changes flow capacity progressively as the stem travels. Use the actual fluid, inlet and outlet pressures, operating temperatures and flow range to select capacity. A nominal pipe size alone gives no basis for choosing the full-port or reduced-capacity trim. Shut-off performance also depends on seat and stem sealing, and on whether the selected trim is balanced.

Use the small-bore KE7 pressure and temperature envelope for the configuration quoted. Ask for the flange class and pressure-temperature rating to be stated explicitly, especially when replacing an installed PN16-marked unit. Verify the existing face-to-face dimension and flange drilling against the order description. The large-bore KE73 product page covers the larger body, which uses a separate technical sheet, travel and actuator selection. Its published dimensions and capacity figures are outside this assembly’s scope.

Check the actuator against the required shut-off duty

The PN9123E uses a rolling diaphragm and a spring-extend assembly. Its specified spring range is 2.0–4.0 bar and the actuator frame has a maximum operating inlet pressure of 6 bar g. Spring range, pressure delivered by the positioner, and maximum operating pressure are separate figures. A spring range is part of the actuator specification and cannot be used alone to set the air regulator or establish that the valve will seat at the design differential pressure.

Determine the highest differential pressure the assembly must overcome during closure and the air pressure actually available at the package. The manufacturer’s tables distinguish flow direction, trim capacity, stem sealing, seat type and leakage class. Use the row for the selected configuration and apply the valve pressure-temperature limit separately. Agree the required loss-of-air response before commissioning and prove the final position on the assembled valve. The actuator spring direction describes spindle motion and the feedback setting determines the valve response to changes in electrical command.

EP6 positioner housing and pneumatic output gauge from the manufacturer technical sheet
EP6 positioner and pneumatic gauge. Source TI-P703-01, page 1.

Specify the linear EP6 and the mounting arrangement

Select a linear, single-acting EP6 electro-pneumatic positioner for the spring-return actuator. For central mounting, the applicable manufacturer table shows the EY3 linkage kit for a PN9100 frame on the small-bore Spira-trol valve. Confirm the chosen EP6 ordering code, actual mounting orientation and 20 mm linkage position before purchase. The feedback lever needs to be aligned at mid-travel, span needs to match the measured stem travel, and the command direction needs to match the process control strategy.

Provide dry, oil-free instrument air to ISO 8573-1:2010 Class 3:3:2, with a suitably regulated supply. The positioner can accept a wider supply range than the actuator’s maximum pressure, so size and set the air supply against both components and the force requirement. Keep room to reach its cover, gauge, cable entry and vent. If the process environment requires a certified configuration, select the exact approved positioner variant before applying any hazardous-area rating to the assembly.

Coordinate installation and commissioning

Plan removal space for the actuator above the valve and access for the positioner feedback linkage. Follow the flow marking and check pipe support, isolation and any bypass arrangement against the plant requirements. Commission the pneumatic and electrical sides together so full travel, stem response, leakage, command direction and behavior on loss of signal or supply can each be checked. Confirm the installed positioner settings after any intervention that changes actuator preload or stem linkage.

What to include in the inquiry

For a replacement, provide the complete valve nameplate data, the actuator’s model and spring information, and the positioner’s ordering code. For a new installation, distinguish the normal modulating duty from the most demanding shut-off case, since these may occur at different process conditions. Ask the quotation to identify the selected valve, actuator and positioner together with the linkage and any separately ordered accessories. This gives installers a reliable basis for checking the delivered equipment against the design before commissioning.

  • Fluid, minimum and maximum flow, valve inlet and outlet pressures, operating temperature and maximum shut-off differential pressure.
  • Nominal size, flange standard and rating, required trim capacity, seat and leakage requirement, stem sealing and any balancing requirement.
  • Available instrument-air pressure, required position on loss of air, electrical command direction, EP6 version and mounting orientation.
  • Plant installation conditions, documentation requirements and any additional air treatment or accessories to be quoted separately.

The technical information below sets out the component ratings that govern this assembly. The installation and maintenance guide explains the work sequence and identifies the original component instructions for commissioning and service.

Technical Information

Scope: small-bore EN K-series selection (TI-S24-71, Issue 20), the PN9123E spring-extend actuator (TI-P357-30, Issue 17) and the linear single-acting EP6 (TI-P703-01, Issue 3). Apply the applicable valve and actuator selection limits together.

KE73 valve body and trim

Valve selection basis
PropertyApplicable information
Valve constructionTwo-port, single-seat globe valve with cage-retained seat. Flanged KE73 body, spheroidal graphite cast iron.
Flow characteristic and rangeabilityEqual percentage, 50:1.
Travel basis20 mm (0.79 in) for the DN15–DN50 size band under review.
Body and connectionUse the applicable small-bore KE7 design and flange pressure-temperature data. The technical sheet uses a PN25 body for sizes without a separate PN16 body. Confirm the exact flange configuration.
Metal seat leakageIEC 60534-4 Class IV standard, Class V on request where available.
Resilient or balanced trimThe sheet lists Class VI for the specified PEEK or PTFE seat arrangements and Class IV for balanced trim. Confirm the applicable construction, temperature and differential pressure.
Standard equal-percentage trim values in the 20 mm travel band, from TI-S24-71 page 6
Nominal sizeFull-port KvReduced trim 1Reduced trim 2Reduced trim 3
DN154.02.51.61.0
DN206.34.02.51.6
DN2510.06.34.02.5
DN3216.010.06.34.0
DN4025.016.010.06.3
DN5036.025.016.010.0

The PN25 body design point is 25 bar g at 120 °C (IM-S24-42, section 2.5). Apply the complete pressure-temperature curve and the limits of the flange, packing and trim selected. For example, the published PEEK seat temperature limit is 220 °C and the standard PTFE chevron packing maximum is 250 °C, subject to the manufacturer’s continuous-operation guidance. These component limits do not define a combined operating point.

Use the original small-bore valve and actuator differential-pressure tables for the ordered seating, stem seal, flow direction and Kvs. A maximum value from a different row does not establish shut-off performance for this package.

PN9123E diaphragm actuator

PN9100 frame outline used as the construction reference for the PN9123E actuator
Actuator frame outline. Source TI-P357-30, page 1.
Actuator selection data
PropertyValue
Spring action and travelSpring extend, 20 mm.
Diaphragm area and spring range100 cm², 2.0–4.0 bar.
Maximum operating inlet pressure6 bar g.
Air connection¼ inch NPT.
Standard reinforced NBR diaphragm temperature range−20 to +110 °C. Apply the positioner and installed configuration limits as well.
Published actuator force at selected motive pressures1,000 N at 5 bar and 2,000 N at 6 bar. These are the actuator table values, distinct from the close-off rating of the assembled valve.

EP6 linear positioner and linkage

Linear positioner mounted on a pneumatic actuator, with the feedback linkage shown
Linear positioner installation example. Source IM-P703-02, figure 5, page 11.
Positioner and mounting data
PropertyApplicable information
Input4–20 mA. Input impedance 250 ± 15 Ω as specified. Minimum 8 mA span for split range where specified.
Published linear travel range20–150 mm; the target linkage is set to the valve’s 20 mm travel.
Operating supply pressure range1.4–7.0 bar, subject to the actuator limit of 6 bar g and the actual duty.
Instrument air qualityISO 8573-1:2010 Class 3:3:2.
Connections¼ inch NPT female for air. M20 cable entry and 0.5–2.5 mm² conductors for the standard unit.
Standard ambient range and enclosure−20 to +70 °C; IP66. Verify the actual variant and enclosure installation.
Central mountingEY3 for the PN9100 frame on Spira-trol DN15–DN50. Confirm linkage, orientation and positioner ordering code.

Installation and Maintenance Guide

Source instructions: IM-S24-42, Issue 16 for the valve; IM-P357-29, Issue 21 for the actuator; and IM-P703-02, Issue 5 for the standard positioner. Follow the complete instructions for the equipment supplied and the applicable plant safety procedures. Where a certified positioner is ordered, use the matching approval and instructions.

Safety before fit-up or servicing

  • Use competent personnel, appropriate work permits, personal protection and suitable lifting arrangements. Compressed-air venting can damage hearing. Wear ear protection when operating near venting equipment and when commissioning the positioner.
  • Assess hazards from hot surfaces, fluid residues, stored pressure, electrical power, spring energy and unexpected motion. Isolate the valve upstream and downstream, vent safely to atmosphere, allow cooling, and isolate the control signal and air supply. A zero gauge indication alone does not establish that the system is safe. Keep hands clear of the actuator yoke and stem on an energised system.
  • Support the pipework and the valve assembly. Use approved lifting methods. Do not lift the valve by the actuator. Do not obstruct the stem or change seating load by placing objects in the yoke. The actuator spring housing can retain stored energy after pneumatic isolation. Follow the actuator manual for any disassembly.

Valve installation

Confirm materials, the pressure-temperature envelope, accessories, bolting and gaskets. Provide overpressure protection if required by the system. Clear the pipework of debris and install to the body flow marking. The manual prefers horizontal pipework with the actuator above the valve. Provide space for actuator withdrawal. Where the plant arrangement calls for it, use upstream and downstream isolating valves and a manual bypass. Open isolating valves slowly and check leakage and operation.

Spira-trol orientation and example horizontal installation with strainer, isolating valves and bypass
Orientation and example installation. Source IM-S24-42, figures 4 and 5, page 45.

Spring-extend actuator fitting and travel check

  1. Use the stem adaptor, setting screw, retaining parts and indicator arrangement in the actuator instructions. Under controlled conditions, position the actuator at mid-travel, place the yoke on the valve bonnet shoulder and hand-tighten the mounting nut. Fit the valve adaptor and seat the plug as instructed.
  2. Follow the fitting setting-pressure table for the PN9123 model, 1.95–2.1 bar g. This is a mechanical setting operation. Adjust the screw to meet the valve adaptor and secure the locknut. Carefully vent the control air and tighten the locking screws to 6 ± 1 N·m. Recheck correct travel and follow the full reset procedure if travel is reduced.
  3. Cycle through full travel four times for alignment. Follow the manufacturer’s specified torque for the actual mounting nut and stem. The instructions require the plug to be off the seat for final tightening and the actuator stem to be held with a second spanner to avoid diaphragm damage.
Spring-extend actuator section with stem linkage, setting parts and mounting nut callouts
Actuator and valve connection at mid-travel. Source IM-P357-29, figure 4, page 13.

EP6 mounting, air and electrical connections

  • Use the applicable central bracket and feedback hardware. Engage the feedback pin in the lever, verify the spring placement and make the feedback lever horizontal at mid-travel. Select the locator mark for the actual 20 mm stroke. Orient the vent cover downward for drainage and leave access to the enclosure and terminals.
  • Provide clean, dry air to the stated class. Connect the supply and output as shown in the single-acting linear diagram for the selected mounting and action. The manual calls for tubing of at least 6 mm outside diameter between the positioner and actuator. Check for leaks and respect the actuator pressure limit, including during manual operation.
  • Connect the 4–20 mA input with the correct polarity and earth. Use a suitable gland and the specified conductor cross-section. The manual requires less than 1 Ω between the earth post and local earth.

Commissioning and maintenance checks

With the process in a safe condition, check the command direction and feedback action for central mounting. At the initial current (4 or 20 mA for the selected action), set zero. Apply the opposite endpoint and check stem travel. Adjust span and then recheck zero until both are correct. Tighten the span lock screw. Confirm the travel at both ends and intermediate steps, then prove the required shutdown behavior. If the positioner’s manual bypass is used during setup, check allowable actuator pressure before use and return the switch to Auto.

Check the air filter and drain it as needed, confirm regulator pressure, inspect linkage and stem motion, and clean the positioner with a damp cloth or antistatic product. For no response, check signal and air, linkage engagement and zero/span. For hunting, check pneumatic stability, feedback and friction. Use the original manuals for service torque, replacement procedures and unresolved faults. Restore protection and repeat functional tests after service.