3749081 Spira-trol PTFE Stem Seal Kit for KE73

Control systems > Control valves

3749081 Spira-trol PTFE Stem Seal Kit for KE73

Replacement PTFE stem seal kit for DN32–DN50 Spira-trol KE73 control valves configured with standard P-type stem packing.

Genuine Spirax Sarco industrial steam product Engineered for energy efficiency and system safety Backed by worldwide application engineering support

Quick facts

Model / Code3749081
CategoryControl valves
ManufacturerSpirax Sarco

PTFE stem packing for DN32–DN50 KE73 control valves

The Spirax Sarco 3749081 is a PTFE stem seal kit for DN32–DN50 Spira-trol KE73 control valves configured with standard P-type PTFE stem packing. It replaces the packing around the moving valve stem where it passes through the bonnet. In the Spira-trol K-series spare-parts drawing, the bracket marked C identifies the PTFE stem packing group.

As the actuator moves the stem to position the plug, the stem passes through the packing in the bonnet. This creates a moving sealing interface. The bonnet-to-body joint uses a separate gasket, and the plug and seat form the shut-off interface inside the valve. Knowing which of these interfaces is leaking helps determine which parts the service team needs.

Exploded view of the Spira-trol item C PTFE stem packing group
The bracket identifies the PTFE stem packing group C. The original drawing includes neighbouring parts for orientation. Source TI-S24-71, page 21.

Check the full valve designation and the installed packing

Start with the complete description on the KE73 valve body label and confirm the nominal valve size. The DN32–DN50 group includes DN32, DN40 and DN50. The valve designation also identifies the stem sealing option separately from the seating, trim and bonnet options. A match on the KE73 family name and nominal size alone leaves those configuration details unresolved.

Read the stem-sealing field specifically. The manufacturer uses P for standard PTFE packing, N for PTFE with a Nitronic bush, V for vacuum-service PTFE, and separate codes for graphite and bellows configurations. The P in the stem-sealing field identifies a different component from a seating code. Similarly, C on the exploded spare-parts drawing identifies the packing group, while C in the seating field refers to the Steam-Tight seat option.

Where the valve has been rebuilt or its packing or bonnet changed, compare the nameplate with the service records and the currently fitted configuration. Confirm the bonnet style and any conversion before ordering. The Spira-trol KE73 control valve reference provides family context. For the installed valve, use the applicable data sheet, full valve designation and packing configuration to confirm fit and operating limits.

Identify the leakage path before specifying the repair

At the top of the bonnet. If leakage appears around the stem where it exits the gland, the manufacturer’s fault-finding guide points to the condition and previous assembly of the stem seals. It also calls for checking the operating pressure, temperature and fluid compatibility. Once the valve has been safely isolated, examine the stem surface. Scoring or deposits can cause early failure of the new packing, so a packing replacement alone may leave the underlying problem unresolved.

At the joint between the valve body and bonnet. The guide lists the bonnet gasket, bolting and operation outside the pressure-temperature range as possible causes. The gasket has its own spare-parts listing. If the planned inspection involves lifting the bonnet, include the correct replacement gasket in the service scope because the manual calls for removing the used gasket and fitting a new one during reassembly.

Through the valve when it is commanded closed. If downstream pressure or temperature rises while the valve is shut, inspect the seat and plug, possible trapped debris, and whether the actuator and positioner bring the valve to its closed position. These checks help identify whether the shut-off problem is in the trim or in the closing action. The PTFE stem kit addresses the gland around the stem.

Section through the Spira-trol PTFE stem gland with numbered parts surrounding the stem
Section view showing where the PTFE packing fits around the stem inside the bonnet. Source IM-S24-42, Figure 9, page 49.

Identify the other parts before opening the valve

Use the exploded drawing to distinguish the stem seal from the other service items. The manufacturer groups the body gaskets, the plug-and-seat assembly and the soft seat seal under their own references. Figure 9 then shows the installed relationship of the stem, gland nut, scraper ring and packing. Together, the figures help identify the correct service area and separate the items to confirm in the quotation from the parts shown for orientation.

When the work includes removal of the actuator or bonnet, have the instructions for both the fitted actuator and the valve available. The PTFE procedure sets the final gland adjustment after the bonnet is back in place. The return-to-service sequence includes checking free plug movement during assembly and checking for gland leakage after reinstating the valve.

What to include in the inquiry

  • Give part number 3749081, the quantity required and the nominal size of each valve being serviced.
  • Provide a legible photo of the full valve body label, including the configuration following KE73.
  • Identify any change to the stem packing or bonnet made during an earlier repair.
  • Describe where the leakage appears and whether it occurs during travel, at the bonnet joint or with the valve commanded closed.
  • List separately any bonnet gasket or other service parts required for the same maintenance work.

Technical Information

Scope is limited to the standard PTFE stem packing configuration and the listed spare-part size grouping. The applicable valve data sheet determines the pressure and temperature limits for the installed valve.

Part identification and ordering checks
Part number3749081
Valve applicationSpira-trol KE73 control valves with standard P-type PTFE stem packing. Check the complete valve designation and existing gland configuration.
Valve size groupDN32, DN40 and DN50, subject to confirmation of the valve type and stem sealing configuration.
Packing typePTFE stem packing. The manufacturer identifies the standard PTFE stem sealing option as P.
Diagram referenceC in the standard spare-parts diagram. The same letter may have a different meaning in another field of a valve selection code.
Associated spare partsThe non-bellows valve gasket set and the soft seat seal are listed separately from the stem packing.
Selection referenceTI-S24-71, Issue 20, pages 21 and 23. Specify the valve size and full valve description when ordering.

The stem-sealing field and the seat field must be read independently in the Spira-trol selection guide. In the stem-sealing field, P denotes the standard PTFE option, N denotes PTFE with a Nitronic bush, and V denotes the vacuum-service PTFE option. These are distinct valve configurations.

Installation and Maintenance

The sequence below covers the relevant PTFE gland service in IM-S24-42, Issue 16, sections 4.1–4.4 and 4.7. Follow the full manufacturer instructions for the installed valve and actuator. Use the component sequence in Figure 9 for the applicable arrangement.

  1. Isolate the valve and actuator. Isolate upstream and downstream, release pressure and clear process media. Disable and isolate the control system to prevent unexpected movement. Remove the actuator according to its own instructions.
  2. Remove the bonnet assembly. Remove the appropriate bonnet fixings and lift off the assembly. Remove and discard the used body gasket as instructed in section 4.3.
  3. Remove the old packing. Take off the locknut and gland nut, withdraw the plug and stem, and remove the scraper ring and used gland components. Clean the gland nut groove, bore and packing cavity. Inspect the stem for scoring or deposits before reusing it.
  4. Install the new packing in the documented order. Fit the gland components as shown in Figure 9. Remove the plastic installation tool, fit the scraper ring and start the gland nut as instructed. Avoid substantial compression before the bonnet is reinstalled.
  5. Refit and adjust. Follow section 4.7 and the tightening table for the actual valve configuration. Fit a new bonnet gasket and centre the plug in the seat. Follow the staged bonnet tightening and plug movement checks in section 4.7. For its DN15–DN100 PTFE assembly, the manual specifies metal-to-metal contact with the bonnet and a gland nut torque of 20 N·m. Confirm the applicable instructions for the installed valve. Refit the locknut and actuator, then check the gland for leakage after return to service.

Talk to our technical team

Contact Spirax Sarco for product selection, documentation or replacement guidance.